Application
These power and control cables are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protections are needed. Its mechanical and physical properties and electrical performance meet the requirements of national standard GB/T12706- 2008 and international standard IEC60502-2004
Operating Characteristics
- Cable laying temperature: ≥0 – 50°C
- Long-term allowable operating temperature of cable conductor: ≤70°C
- Rated voltage: U0/U =0.6/1 (Um=1.2) kV
- Service Temperature -15OC to 60OC
a. Minimum permissible bending radius for Single core cable: 20D - Finished cable can bear AC 50HZ, 3 KV, 5min withstand test without breakdown.
- Conductor DC resistance meets the requirements of national standard GB/T3956-2008 “Cable Conductor” and international standard IEC60228
Description
- Conductor: Solid plain copper
- Insulation: Polyvinyl chloride (PVC) It has good ageing and mechanical properties
- Sheath Outer: Polyvinyl chloride (PVC) It has good ageing and mechanical properties
Conductor dimensions (mm2) |
Conductor Diameter (mm) |
Insulation thickness (mm) |
Sheath thickness (mm) |
Outer diameter (approximate) (mm) |
Cable weight (Kg/km) |
4 | 2.3 | 1 | 1.4 | 7.1 | 86 |
6 | 2.8 | 1 | 1.4 | 7.6 | 110 |
10 | 3.9 | 1 | 1.4 | 8.7 | 158 |
16 | 5 | 1 | 1.4 | 9.8 | 224 |
25 | 6 | 1.2 | 1.4 | 11.2 | 325 |
35 | 7 | 1.2 | 1.4 | 12.4 | 429 |
50 | 8.4 | 1.4 | 1.4 | 14.0 | 590 |
70 | 10 | 1.4 | 1.4 | 15.6 | 791 |
95 | 11.7 | 1.6 | 1.5 | 17.9 | 1062 |
120 | 13.1 | 1.6 | 1.5 | 19.3 | 1306 |
150 | 14.6 | 1.8 | 1.6 | 21.4 | 1625 |
185 | 16.3 | 2 | 1.7 | 23.7 | 1998 |